- 日本 | 日本語
- United States | English
- Deutschland | Deutsch
Pressure Controller for Transmitter Calibration|Automated Multi-Point Upscale and Downscale Testing with Low-Hysteresis Control
Automatically applies the pressures required for transmitter calibration at multiple pressure points, accurately and stably
Calibrating the differential pressure and pressure transmitters used for process control in plants involves checking their output at multiple pressure points during pressurization and depressurization. The MC300 Pressure Controller automatically steps the pressure up and down through the set pressure points and applies pressure accurately with low hysteresis. Combined with the MT300 Reference Pressure Gauge, it enables comparison calibration, and an MT300 option eliminates the need for an external power supply or multimeter.
Summary
Challenge
Transmitter calibration requires manually adjusting the pressure to each pressure point, on both rising and falling pressure.
Solution
The MC300 automatically steps the pressure up and down through multiple preset pressure points.
Expected Benefits
Manual pressure adjustment at each pressure point is no longer necessary, which can reduce the calibration workload.

Yokogawa Test & Measurement Corporation
Yokogawa Test & Measurement Corporation is the test and measurement instrument business of the Yokogawa Electric Group. The company develops, manufactures, and sells a wide range of precision measurement solutions, including oscilloscopes, power analyzers, data acquisition systems, optical communication test equipment, and pressure measurement instruments. The Yokogawa Electric Group has a track record of over 100 years in the development and provision of precision measurement instruments. In the field of pressure measurement, the group has accumulated technology over many years and developed a pressure measurement platform built around its proprietary silicon-based resonant sensor technology. Through a product portfolio spanning from lab to field — including the MT300 Reference Pressure Gauge, the CA700 Pressure Calibrator, and the MC300 Pressure Controller — Yokogawa supports customers' pressure measurement needs.
Pressure Controller for Transmitter Calibration
Differential pressure and pressure transmitters used for process control in plants are calibrated periodically by maintenance and calibration technicians. Yokogawa's MC300 Pressure Controller can generate the reference pressure for this calibration and, together with the MT300 Reference Pressure Gauge, automate the application of pressure in calibration tests performed at multiple pressure points.

Challenges in Differential Pressure and Pressure Transmitter Calibration
Performance Requirements for the Reference Standard and Applied Pressure
Because differential pressure and pressure transmitters must deliver high accuracy and stability, the reference standard used to calibrate them needs equal or better performance. The pressure applied to the transmitter and the reference standard must also be accurate and stable during both pressurization and depressurization; otherwise, the transmitter's characteristics cannot be verified correctly.
Manual Pressure Adjustment with Hand Pumps in the Low-Pressure Range
Hand pumps are commonly used in transmitter calibration to adjust pressure manually. Calibrating transmitters in the low-pressure range, in particular, requires pressure control in increments of tens to hundreds of pascals. With a hand pump, the pressure can overshoot or fail to stabilize, so setting it to the target value takes time and repeatability is difficult to ensure.
Time-Consuming Multi-Point Upscale and Downscale Testing
Calibration requires checking the transmitter output at multiple pressure points within the measuring range, both during pressurization and during depressurization. Because each point requires setting the pressure, waiting for it to stabilize, and reading the transmitter output before moving on, the work takes longer as the number of transmitters to be calibrated increases.
Preparing Power Supplies and Measuring Instruments
Verifying transmitter output requires not only a pressure source and a reference standard, but also a power supply for the transmitter and an instrument that measures its output current or voltage. The more instruments involved, the more effort goes into wiring, transport, and setup.
Solution with the MC300 Pressure Controller

Multi-Point Upscale and Downscale Testing with the Auto-Step Function
The MC300's auto-step function automatically outputs pressure in sequence according to multiple preset pressure points. When the set pressure and the number of divisions (up to 25) are specified to match the transmitter's full scale, equally spaced pressure points are defined from 0 to the set pressure.
During operation, the output moves automatically to the next pressure point at each set interval (10 s to 600 s). The pressure steps up to the set pressure and then steps back down. In transmitter calibration, this function can automate the pressure application needed for multi-point upscale and downscale testing.
Accurate Pressure Application with Low Hysteresis
The MC300 can automatically regulate its output to the set pressure. Its pressure output combines low hysteresis with excellent linearity and repeatability, so pressure can be applied accurately whether it is rising or falling.
For example, in a test with 3 pressurization and depressurization cycles on the 200 kPa range model, the deviation remained within approximately 10 ppm.

The MC300 achieves an output relative accuracy of ±0.04% of full scale* by combining sensing technology based on Yokogawa's proprietary silicon resonant sensor with needle-valve flow control. Yokogawa guarantees this accuracy for 12 months, including drift over time.
*At 23°C±3°C, after zero calibration at atmospheric pressure. Relative to Yokogawa's working standard.
Transmitter Pressure Ranges Covered
The MC300 is available in two gauge pressure models: one with a range up to 10 kPa (MC300-G01) and one with a range up to 200 kPa (MC300-G03). It can be used to calibrate transmitters whose measuring range falls within either of these ranges.
Comparison Calibration with the MT300 Reference Pressure Gauge
Combining the MC300 with the MT300 Reference Pressure Gauge enables comparison calibration with the MT300 serving as the reference standard. The MC300 applies the reference pressure for calibration to both the transmitter and the MT300, and the transmitter output is then checked to confirm that it corresponds to the pressure measured by the MT300.
The MT300 is available with a 24 VDC output and voltage/current measurement option (/DM). With this option, the MT300 can supply 24 VDC to the transmitter and measure its output signal (1–5 V or 4–20 mA). A built-in 250 Ω communication resistor can be switched on or off. The option is available only for the MT300 gauge pressure and absolute pressure models.
| Equipment | Role in Calibration |
|---|---|
| MC300 Pressure Controller | Generates the reference pressure for calibration and applies it to the transmitter and the MT300 |
| MT300 Reference Pressure Gauge (with /DM option) | Serves as the reference standard by measuring the applied pressure; supplies 24 VDC to the transmitter and measures its output |
Expected Benefits of Using the MC300
Automated Pressure Application During Calibration
There is no need to set the pressure by hand at each point, upscale or downscale. The same automated pressure application is also available in comparison calibration with the MT300.
A More Compact Calibration Setup
With the voltage/current measurement option, the MT300 not only measures pressure as the reference standard but also powers the transmitter and measures its output, so there is no need for a separate power supply or multimeter. Fewer instruments are needed, which helps make the calibration setup more compact.
Related Content
MC300 Pressure Controller
The MC300 Pressure Controller applies precise pressures for pressure calibration and testing. It incorporates Yokogawa's proprietary silicon resonant sensor and a needle valve servo mechanism to deliver high-accuracy pressure control. With an output relative accuracy of ±0.04% and a 12-month accuracy guarantee period, it provides stable pressure control over extended operating periods. The MC300 is used across a wide range of process management and production automation applications that require precise pressure control, including production line inspection of pressure sensors and pneumatic devices, compliance testing of blood pressure monitors, leak testing of enclosures, and calibration of differential pressure and pressure transmitters.
About Yokogawa Test & Measurement Corporation

Developing, Manufacturing, and Delivering Precision Measurement Solutions
Yokogawa Test & Measurement Corporation is the test and measurement instrument business of the Yokogawa Electric Group. The company develops, manufactures, and sells a wide range of precision measurement solutions, including oscilloscopes, power analyzers, data acquisition systems, optical communication test equipment, and pressure measurement instruments.
The Yokogawa Electric Group has a track record of over 100 years in the development and provision of precision measurement instruments. In the field of pressure measurement, the group has accumulated technology over many years and developed a pressure measurement platform built around its proprietary silicon-based resonant sensor technology. Through a product portfolio spanning from lab to field — including the MT300 Reference Pressure Gauge, the CA700 Pressure Calibrator, and the MC300 Pressure Controller — Yokogawa supports customers' pressure measurement needs.
| Presenter Name | Yokogawa Test & Measurement Corporation |
|---|---|
| Address | 9-8, Myojin-cho 4-chome, Hachioji-shi, Tokyo 192-8566, Japan — Keio Hachioji Myojin-cho Building |
| Established | July 1954 |
| URL | https://tmi.yokogawa.com/ |